346 WIN-PAK User Guide
Click Add in the ADV area (upper right). In the
ADV definition, set up priorities for each input state
you wish to monitor. When the ADV is completed,
click OK to return to the panel dialogs and complete
the panel definition.
When an active input point is selected, the following
options are available:
Time Zone: To shunt (deactivate) an input point
during a particular time zone, select that time zone
from the list.
Shunt Time: Enter a value (0 to 63) to set the
amount of time that the input point is deactivated
(shunted) when triggered. This can be set in seconds,
minutes or hours by using the selection buttons
directly above the option.
Debounce Time: Enter a value (0 to 255) to set the
amount of time, in seconds, that an input must be in
a changed state before that change is reported. For
example, an input point with a debounce time of 5
must be in active condition for five seconds before it
is reported as an alarm. The same is true when
returning to normal condition. The point would not
report as normal until it was in the normal state for
five seconds. If the value is set to zero, the debounce
time is a minimum of .33 seconds on events going to
normal, but alarms are reported immediately
(debounce time is 0 seconds on alarm).
Supervised: All alarm input points default to
normally closed, non-supervised circuits used to
monitor changes of state. Inputs can also be
configured for normally open circuits and 3-state
supervised circuits. Select this check box to
configure the selected input point as supervised, and
then select your choice of Normally Open, or
Normally Closed