332 WIN-PAK User Guide
Interlocks initiated by an output point change of state
are defined on the Panel Configuration Outputs
window. To edit output interlocking, expand the
Device Map, and right-click the panel you want to
edit. Select Configure and click the Outputs tab.
Component A
From the Name list on the Inputs or Outputs
window select the check box to indicate the input or
output point that will initiate the interlock sequence.
This point will be called (for the purposes of this
explanation) Component A. A change of state on
Component A causes a reaction from Component B.
Select the Interlocking check box to activate the
Interlocking area of the window.
Component B
Select I, O or G for an input point, output point or
group, respectively, then select the Point to react to
a change of state of Component A. This point will
be Component B.
Action 1: Specify the action Component B takes
when Component A goes into an active state [input] or
on [output].
Action 2: Specify the action for Component B to
take when Component A returns to a normal state
[input] or off [output].
The actions available are as follows:
Energize: Turn the point on.
De-Energize: Turn the point off.
Pulse: Energize the point for a set amount of time.
Pulse Off: Turn off a point currently being pulsed.
When relay is energized, it will Pulse Off and then
return to Energized state. (This is rarely used and
must be used in addition to a command file.)