Once a point goes into alarm or trouble, the color
will not return to green. For example, if the first
message from a point or card is Normal, subsequent
Alarm or Trouble conditions change the alarm to red
or yellow.
After that, even if the point returns to a Normal
state, the message stays red (or alternates between
yellow and red). It does not return to green on a
Normal state.
The Count column on the Alarm View window
shows the number of times a point changes state.
Once this message is acknowledged, new Normal
messages are displayed in green.
Using the Alarm View Command Buttons
A set of buttons on the Alarm View window allow
you to easily handle basic, routine alarms tasks.
Acknowledge (Ack): To acknowledge an alarm,
select it from the list of incoming alarms and click
the Ack button. When the alarm is acknowledged, it
moves to the list in the lower pane of the Alarm
View window, unless the auto-clear option is
selected from System Defaults. The background
color of the transaction is now grey and the color of
the alarm text changes as well: green for normal,
yellow for trouble, and red for alarm. This color
changes with each new condition. Transactions
remain in the Acknowledged Alarm section of the
window until they are cleared.
Silence: Allows operator to silence the alarm for 60
seconds without actually acknowledging it. This
feature is enabled in the Alarms Handling section of
the System Default Configuration.
Clear: To clear one or more transactions, select them
from the list and click the Clear button.